Figure 5-2
Vertical Unit Left Handed Steam Inlet
Figure 5-1
Horizontal Unit Right to Left Flow
(Left Hand Header)
Figure 5-3
Vertical Duct Downward Flow
(Left Hand Inlet)
Inlet
Outlet
Drain
Inlet
Outlet Drain
(HumidiPackPlus orientation is similar)
Installation Concepts
Condensate Drainage Options
Condensate discharged from the HumidiPack or HumidiPackPlus separator/header is at essentially
atmospheric pressure. Thus the condensate must be discharged to a drain or pumped. On many
applications, an attempt to lift condensate even a few inches will lead to potential flooding or spitting problems
from the multiple tube bank. For HumidiPackPlus units having a header drain connection and active tube
jacket drain connection, a separate F&T steam trap must be used for each. Avoid master trapping the two
connections to one steam trap. If traps discharge into a common return, install check valves (low opening
pressure) on the outlet of each steam trap.
Typical HumidiPack
®
Duct Installations
(HumidiPackPlus orientation is similar)