Installation Concepts
Condensate Drainage Options
Condensate discharged from the HumidiPack or HumidiPackPlus separator/header is at essentially
atmospheric pressure. Thus the condensate must be discharged to a drain or pumped. On many
applications, an attempt to lift condensate even a few inches will lead to potential flooding or spitting problems
from the multiple tube bank. For HumidiPackPlus units having a header drain connection and active tube
jacket drain connection, a separate F&T steam trap must be used for each. Avoid master trapping the two
connections to one steam trap. If traps discharge into a common return, install check valves (low opening
pressure) on the outlet of each steam trap.