10
Step 9E (EM): Make Electrical
Connections
as recommended by the
manufacturers of the operators and controls.
Also, use Figures 10-1 through 10-3 as a guide.
Be sure wiring is adequate for the requirements
of the system. Check voltage ratings on
operator nameplate.
“EM” Series electric motor operated humidifiers
are furnished with a choice of Honeywell
M9182A operators (24 watts at 24v, 60 Hz
suitable for 120v or 240v with transformer),
Belimo AF24SR or NVF24 electric
motorized operators. These operators
may be controlled by compatible humidity
controllers or electronic humidity panels.
For all EM operators mount operator so
that the motor shaft is parallel to the
floor (or horizontal).
Step 10E: Install and Wire
Humidity Controller as specified by the
design engineer and in accordance with
manufacturer's instructions. If location is
not specified, the controller may be
installed in area controlled or in either the
return air or exhaust air ducts.
Figure 10-1
H915 (Series 90
Humidity Controller
If High Limit Not Used,
Wire (R) Directly to (R)
HC-201 High Limit
Duct Humidity Controller
(When Used)
M9182A (Series 90)
Motorized Operator
Transformer
Fan Interlock
Figure 10-2
Dip Settings Shown Are For
One (1) M9182A Motor With
4-20 mA Control Signal
Input Impedance On Resistor
Board is 66 OHMS
Primary Voltage
120, 208, 240, 480 VAC
Optional Fan
Interlock or
Pressure Switch
(Open on Fault)
AMW#A9023
4-20 mA Humidistat
or Controller
Neg. (-) (+) Pos.
Optional
High Limit
Humidistat
(Open on %RH
Rise) AMW#A8581
Optional
Temperature
Switch (Open on Fault)
AMW#B1564
Figure 10-3
Belimo AF24-SR
or NVF24-MFT-E
Line Voltage
24 VAC
Transformer
B1564 Electric
Temperature
Switch (Optional)
8581
High Limi
Humidista
(Optional)
A9023
Pressure
Switch
(Optional)
Armstrong
0-10 VDC Stat
A18609 or A18610