Figure 3-4. Eight inch clearance (Min.)
should be maintained on discharge side
of coils.
Figure 3-1. The HumidiPack must
have airflow across the entire cross-
section. Avoid fan discharges without
gradually transitioning the duct to the
HumidiPack.
Figure 3-2. The HumidiPack cannot
have daead air space off the discharge
side. When discharging into a fan
intake plenum, allow for vapor trail
length then gradually transition the duct.
Figure 3-5. If temperature controlling devices
must be placed directly downstream from the
HumidiPack, all visible vapor must be ab-
sorbed. This may be a longer distance than
just the specified vapor trail. Consult factory if
questionable applications arise.
Figure 3-3. Coils, duct transitions and
other obstructions must be kept at least
the specified vapor trail length down-
stream from the HumidiPack. This
does not apply to high efficiency filters.
Consult factory on these applications.
Figure 3-7. When installing the HumidiPack directly upstream from a
discharge grill, the minimum distance shall be the specified vapor trail.
It should be noted that visible wisps of vapor can still be seen even
though the length is beyond the vapor trail. This vapor will not
condense on the grill, but may be seen in the room space.
Figure 3-6. All airflow must be directed
through HumidiPack. If HumidiPack is
smaller than the duct cross-section,
HumidiPack should be positioned in
center of duct and all open area should
be blocked off. This is an exception for
some "all active" unit applications.
Coil
Filter
Dead Air
Don't
Beyond
Specified
Vapor
Trail
Less Than
Specified
Vapor Trail
Duct Temp. Contro
l
Don't
Do
Do
Don't
Dead Air
Don't
Do
Maintain
at Least
Specified
Vapor Trail
Less Than 8"
Don't
Discharge
Grill
Beyond
Specified
Vapor Trail
Less Than
Specified
Vapor Trail
Do
Don't